Data Foundry

CPSC recalls 2000

CPSC, Liebert Corp. Announce Recall of Cooling System

U.S. Consumer Product Safety Commission recall (2000-11-08). Hazards: fire. About 1,500 units in the US.

AgencyU.S. Consumer Product Safety Commission
Recall number01503
Published2000-11-08
Last updated2026-04-08
Product categoryAir Conditioners
ProductsMini-Mate2 Environmental Control Units
Firm named in the titleLiebert Corp.
FirmsLiebert Corp., of Columbus, Ohio (manufacturer)
Units (US)1,500
Hazard classesfire
Remedy classesreplace
SoldLiebert Corp. sold these units nationwide, from January 1998 through August 2000, for between $3,000 and $8,000.

Description

The environmental control units are used as a cooling system in computer rooms. The recalled units are 277 volts and 1.5, 2 and 3 tons with electric reheat. The units are mounted in the ceiling and use ducts or special distribution grills to distribute the air.

Hazard

An electric heating element inside the system, that is used primarily in the dehumidification process, can short circuit and produce sparks, posing a smoke and fire risk.

Remedy

For more information about the recall, contact Liebert Corp. for instructions on disconnecting the reheat assembly. Liebert Corp. will install and replace the heating element. Liebert Corp. sent recall notices to known purchasers.

Incidents and injuries

No injuries have been reported.

Machine access

This record, with every extracted field, the source record (contact text and images withheld) and provenance: GET https://api.data.aroqon.com/v1/product-recalls/cpsc-01503. Look up a model number or UPC with /v1/product-recalls/lookup?code=…. About the dataset · free and paid keys.