Data Foundry

CPSC recalls 2001

CPSC, Trane Company Announce Recall of Voyager Heating and Air Conditioning Systems

U.S. Consumer Product Safety Commission recall (2001-01-24). Hazards: carbon monoxide. Models: YCD036C1H, YCD060CWH, YCD048C1H, YCH060C1H, YCH048C1H, YCH060C3H…. About 967 units in the US.

AgencyU.S. Consumer Product Safety Commission
Recall number01507
Published2001-01-24
Last updated2026-04-14
Product categoryAir Conditioners
ProductsTrane Voyager Series Combination Gas Furnace and Electric Air Conditioning Units
Firm named in the titleTrane Company
FirmsThe Trane Company, of Tyler, Texas, a division of American Standard Companies Inc. (manufacturer)
Units (US)967
Model numbersYCD036C1H, YCD060CWH, YCD048C1H, YCH060C1H, YCH048C1H, YCH060C3H, YCD060C1H, YCH060C4H, YCD060C3H, YCD060C4H
Hazard classescarbon monoxide
Remedy classesreplace, inspect
Trade facetshvac

Description

The Voyager series of light commercial rooftop air conditioners with electric cooling and gas-fired heat exchangers, which are installed in schools and commercial applications, have 120,000 to 135,00 BTU heating capacity and three- to five-ton cooling capacity in horizontal and downflow configurations. The Voyager series has been manufactured by Trane since 1988 and is distributed under the Trane® and American Standard® brand names. The recalled units were manufactured between June 1, 2000 and August 16, 2000 and have serial numbers beginning with R21 through and including R33. The recalled products include the following model designations: YCD036C1H_ _ _ YCD060CWH_ _ _ YCD048C1H_ _ _ YCH060C1H_ _ _ YCH048C1H_ _ _ YCH060C3H_ _ _ YCD060C1H_ _ _ YCH060C4H_ _ _ YCD060C1H_ _ _ YCD060C3H_ _ _ YCD060C4H_ _ _ A name plate bearing each unit's model and serial number is located on the outside sheet metal at the end of the unit where the propeller fan is visible on top, directly to the left of the exposed outdoor coils.

Hazard

One of the three internal flue gas tubes extending from the heat exchanger can separate from the heat exchanger. This could allow flue gases, including carbon monoxide, to enter the building airstream. This could result in serious injury or death to building occupants.

Remedy

Call the local independent Trane or American Standard dealer for a free inspection and replacement, if needed. Trane will completely replace the heat exchanger end plate and internal flue gas tube assemblies in all recalled units at no cost to the consumer.

Incidents and injuries

None reported.

Machine access

This record, with every extracted field, the source record (contact text and images withheld) and provenance: GET https://api.data.aroqon.com/v1/product-recalls/cpsc-01507. Look up a model number or UPC with /v1/product-recalls/lookup?code=…. About the dataset · free and paid keys.

Source: U.S. Consumer Product Safety Commission recall notice (US Government work). Not affiliated with or endorsed by CPSC. Structured by Data Foundry (product-recall-structuring@2); last changed 2026-09-28. Always confirm with the agency notice.