Data Foundry

CPSC recalls 2005

CPSC, Honeywell Sensing and Controls Announce Recall of Thermal Switches

U.S. Consumer Product Safety Commission recall (2005-03-08). Hazards: fire. Models: 2455RA, 2455RM. About 113,500 units in the US.

AgencyU.S. Consumer Product Safety Commission
Recall number05548
Published2005-03-08
Last updated2024-12-02
Product categorySwitches
ProductsSnap Action Thermal Switches
Firm named in the titleHoneywell Sensing and Controls
FirmsHoneywell Sensing and Controls, of Freeport, Ill. (manufacturer)
Manufactured inChina
Units (US)113,500
Model numbers2455RA, 2455RM
Hazard classesfire
Remedy classesreplace
SoldHoneywell Sensing and Controls to authorized distributors and manufacturers nationwide, from July 2004 through August 2004, for between $1 and $2.

Description

These "Snap Action" thermal switches were sold under the model number 2450A, 2455RA, or 2455RM. They have model numbers and date codes stamped on the sensing surface or end cap. Following are those model numbers and date codes that are part of the corrective action: Model Number Date Codes Part of Corrective Action 2455RA and 2450A Z0412, Z0413, Z0414, Z0415, Z0416, Z0417, Z0418, Z0419, Z0420, Z0421, Z0427, Z0429, Z0430, Z0431,Z0432, Z0434, Z0435, Z0436, Z0437 2455RM Z0421, Z0427, Z0429, Z0430, Z0431, Z0432, Z0434, Z0435, Z0436, Z0437

Hazard

When these switches are used in fire or HVAC dampers and heat detectors, they could fail to operate, causing the damper not to close or causing the heat detector not to alarm, if there is a fire.

Remedy

Honeywell Sensing and Controls will provide a free replacement switch.

Incidents and injuries

None reported.

Machine access

This record, with every extracted field, the source record (contact text and images withheld) and provenance: GET https://api.data.aroqon.com/v1/product-recalls/cpsc-05548. Look up a model number or UPC with /v1/product-recalls/lookup?code=…. About the dataset · free and paid keys.

Source: U.S. Consumer Product Safety Commission recall notice (US Government work). Not affiliated with or endorsed by CPSC. Structured by Data Foundry (product-recall-structuring@2); last changed 2026-09-28. Always confirm with the agency notice.