Data Foundry

CPSC recalls 2006

Square D Recalls Safety Switches Due to Shock or Electrocution Hazard

U.S. Consumer Product Safety Commission recall (2006-12-15). Hazards: electric shock. About 27,600 units in the US.

AgencyU.S. Consumer Product Safety Commission
Recall number07062
Published2006-12-15
Last updated2014-05-23
Product categorySwitches
ProductsGeneral Duty Safety Switches
Firm named in the titleSquare D
FirmsSquare D Co., of Palatine, Ill. (manufacturer)
Manufactured inMexico
Units (US)27,600
Hazard classeselectric shock
Remedy classesreplace
SoldElectrical distributors and retailers from September 2006 through November 2006 for between $120 and $300.

Description

The recall includes General Duty 30- and 60-ampere, 240-volt, 1-phase and 3-phase NEMA 3R safety switches. The switches are typically used to control the flow of electricity to outdoor motorized units that are hardwired to a household or business electrical system such as outdoor air conditioning and heating (HVAC) equipment. The switches contain "ON" and "OFF" positions. The "OFF" position is designed to cut the flow of electricity to an outdoor motorized unit to protect the person who is servicing the unit. The recalled switches have the following date codes and catalog number printed on bottom of the wiring label inside the front cover or on bottom of the package label. Date Codes 06371 through 06446 Catalog Numbers D211NRB D211NRBBP D211NRBCP D221NRB D221NRBCP D321NRB D321NRBCP DU221RB DU222RB DU321RB DU322RB

Hazard

The safety switch can continue to supply electricity even after being placed in the "OFF" position. This poses the risk of an electric shock or electrocution hazard to consumers.

Remedy

Consumers should return the uninstalled safety switches to the retailer or distributor where purchased for a free replacement unit. Installed safety switches will be replaced free of charge by contacting the firm.

Incidents and injuries

No incidents or injuries have been reported.

Machine access

This record, with every extracted field, the source record (contact text and images withheld) and provenance: GET https://api.data.aroqon.com/v1/product-recalls/cpsc-07062. Look up a model number or UPC with /v1/product-recalls/lookup?code=…. About the dataset · free and paid keys.

Source: U.S. Consumer Product Safety Commission recall notice (US Government work). Not affiliated with or endorsed by CPSC. Structured by Data Foundry (product-recall-structuring@2); last changed 2026-09-28. Always confirm with the agency notice.