Data Foundry

CPSC recalls 2010

Fire Alarm Control Panels Recalled by Fire-Lite Alarms Due to Alert Failure

U.S. Consumer Product Safety Commission recall (2010-10-05). Hazards: fire. Models: MS-9600LS. About 530 units in the US.

AgencyU.S. Consumer Product Safety Commission
Recall number11702
Published2010-10-05
Last updated2016-07-05
Product categoryFire or Smoke Alarms
ProductsFire Alarm Control Panel
Firm named in the titleFire-Lite Alarms
FirmsFire-Lite Alarms of Northford, Conn. (manufacturer)
Manufactured inUnited States
Units (US)530
Model numbersMS-9600LS
Hazard classesfire
Remedy classesnew instructions
SoldAuthorized wholesalers and distributors nationwide from October 2008 through March 2010 for between about $875 for the expander module and $2,285 for the control panel. These distributors resold and/or installed the control panels and modules for use in commercial facilities such as office buildings.

Description

This recall involves the Fire-Lite model MS-9600LS Series control panel that uses the SLC-2LS Expander Module. The following control panel model numbers included in this recall are: MS-9600LS, MS-9600LSC, MS-9600LSE, MS-9600UDLS, MS-9600UDLSE, UNIMODE9600LS and UNIMODE9600UDLS. The control panel is the main portion of the fire alarm system. The software in the expander module tells the system to sound an alarm and flash warning lights. The words "Fire-Lite Alarms by Honeywell" and the model number are located on the front of the fire alarm control panel.

Hazard

The recalled fire alarm control panels used with an SLC-2LS expander module can fail to sound an alarm in the event of a fire.

Remedy

Building managers should contact Fire-Lite Alarms for a free software upgrade. Fire-Lite Alarms is contacting its customers directly.

Incidents and injuries

None reported.