Data Foundry

CPSC recalls 2012

Gems Sensors Recalls Pressure Transducers Used in Fire Pump Controllers Due to Risk of Failure in a Fire

U.S. Consumer Product Safety Commission recall (2012-04-24). Hazards: fire. About 25,000 units in the US.

AgencyU.S. Consumer Product Safety Commission
Recall number12156
Published2012-04-24
Last updated2016-04-18
Product categorySprinklers (Fire)
ProductsGems 3100 Pressure Detectors/Transducers
Firm named in the titleGems Sensors
FirmsGems Sensors Inc., of Plainville, Conn. (importer)
Manufactured inEngland
Units (US)25,000
Hazard classesfire
Remedy classesreplace, new instructions, inspect
SoldGems sold the recalled 3100 Pressure Transducers directly to end-users and through distributors from January 2006 through February 2012 for about $250.

Description

The Gems 3100 Pressure Transducer is used to detect pressure in a range of applications, including the detection of water pressure as part of a fire pump controller in a fire suppression sprinkler system. The transducer has "Gems Sensors & Controls," as well as the 18-digit part number, printed on a label affixed to the center of the transducer. Part numbers beginning with "3100" are included in this recall.

Hazard

The transducer can fail to accurately detect water pressure in a fire suppression sprinkler system. This could cause the sprinkler system to fail to activate and pump water to the sprinklers in the event of a fire.

Remedy

Contact Gems to receive enhanced twice monthly inspection instructions and information about a free replacement transducer, when warranted. End-users who use the 3100 Pressure Transducer in other applications in which water pressure is measured should contact Gems to determine if their units are affected.

Incidents and injuries

None.

Machine access

This record, with every extracted field, the source record (contact text and images withheld) and provenance: GET https://api.data.aroqon.com/v1/product-recalls/cpsc-12156. Look up a model number or UPC with /v1/product-recalls/lookup?code=…. About the dataset · free and paid keys.

Source: U.S. Consumer Product Safety Commission recall notice (US Government work). Not affiliated with or endorsed by CPSC. Structured by Data Foundry (product-recall-structuring@2); last changed 2026-09-28. Always confirm with the agency notice.