CPSC recalls 2014

Schneider Electric Recalls Square D-Brand F and K Frame Circuit Breakers Due to Fire Hazard

U.S. Consumer Product Safety Commission recall (2014-03-18). Hazards: fire, burn, electric shock. About 28,400 units in the US.

AgencyU.S. Consumer Product Safety Commission
Recall number14134
Published2014-03-18
Last updated2015-01-08
Product categoryElectric Wire or Wiring Systems
ProductsSquare D branded, molded case F and K frame circuit breakers
Firm named in the titleSchneider Electric
FirmsSchneider Electric USA Inc., of Palatine, Ill. (importer)
Manufactured inMexico
Units (US)28,400
Hazard classesfire, burn, electric shock
Remedy classesreplace
Trade facetselectrical
SoldAuthorized Schneider Electric distributors nationwide such as Border States Electric Supply, Crescent Electric Supply Co., Dealers Electric Supply Co., Graybar Electric Co., Rexel, W.W. Grainger from May 2013 to June 2013 for between $200 and $9,260.

Description

This recall involves Square D brand models FA, FH, FI and FY one-, two- and three-pole circuit breakers rated 15 to 100 amps, and model KI two- and three-pole circuit breakers rated 110 to 250 amps. The F model breakers were manufactured May 8, 2013 through June 10, 2013 and have date codes 13193 through 13241. The K models were manufactured May 2, 2013 through June 21, 2013 and have date codes 13184 through 13255. The date codes are YYWWD format (example: 13184 = year 2013, week 18, day of the work week 4/ Thursday). The circuit breakers have a yellow label with the words "Square D" or the Square D logo. Model information can be found on the faceplate.

Hazard

The circuit breaker can fail to trip when an overload occurs, posing the risk of fire, burn and electric shock.

Remedy

Consumers should immediately check to see if they have the recalled circuit breakers. Consumers with uninstalled products will receive a replacement. Installed products will be replaced at no charge to the customer with an allowance of up to $300 per site to cover labor costs.

Incidents and injuries

None reported.

Machine access

This record, with every extracted field, the source record (contact text and images withheld) and provenance: GET https://api.data.aroqon.com/v1/product-recalls/cpsc-14134. Look up a model number or UPC with /v1/product-recalls/lookup?code=…. About the dataset · free and paid keys.

Source: U.S. Consumer Product Safety Commission recall notice (US Government work). Not affiliated with or endorsed by CPSC. Structured by Data Foundry (product-recall-structuring@2); last changed 2026-09-28. Always confirm with the agency notice.