Bosch Security Systems Recalls Fire Control Panels Due to Fire Alarm Failure (Recall Alert)

U.S. Consumer Product Safety Commission recall (2014-01-16). Hazards: fire. Models: D9412GV4, D7412GV4, D7212GV4. About 2,000 units in the US.

AgencyU.S. Consumer Product Safety Commission
Recall number14711
Published2014-01-16
Last updated2014-05-23
Product categoryFire or Smoke Alarms
ProductsBosch GV4 Fire Alarm Control Panels
Firm named in the titleBosch Security Systems
FirmsBosch Security Systems Inc., of Fairport, N.Y. (manufacturer)
Manufactured inChina
Units (US)2,000
Model numbersD9412GV4, D7412GV4, D7212GV4
Hazard classesfire
Remedy classesrepair
SoldAuthorized distributors and certified professional installers nationwide from January 2012 to December 2012. The circuit module sold for about $90.

Description

The recall involves G-series Fire Alarm Control Panels that are professionally installed and have model numbers that end in GV4 and use D192G Notification Appliance Circuit (NAC) modules. The NAC module monitors the circuit connections and signals when alarms are not operational. The Bosch name, logo and model number D9412GV4, D7412GV4 or D7212GV4 are on the board of recalled GV4 fire alarm control panels. The control panels and modules are used in residences and commercial facilities and can be mounted inside a variety of enclosures with a minimum size of 16 inches x 16 inches x 3.5 inches, which may or may not be labeled with the Bosch name or logo.

Hazard

The notification appliance circuit module can cause the panels to fail to activate an audible or visual alarm in the event of a fire.

Remedy

Consumers who have a recalled GV4 control panel with a D192G NAC module should contact Bosch or their certified professional installer for a free repair. Bosch has contacted their distributors and installers and sent installers a service bulletin telling them how to correct the problem.

Incidents and injuries

None reported.