U.S. Consumer Product Safety Commission recall (1977-07-29). Hazards: fire, burn.

AgencyU.S. Consumer Product Safety Commission
Recall number77081
Published1977-07-29
Last updated2015-02-04
Product categorySmoke Detectors/Alarms
ProductsMaster battery-operated smoke alarms
FirmsMaster Lock (manufacturer)
Hazard classesfire, burn
Trade facetselectrical, building products

Description

July 29, 1977 Release # 77-081 WASHINGTON, D.C. (July 29)-- Master Lock Company, Milwaukee, Wisconsin, in cooperation with the U.S. Consumer Product Safety Commission (CPSC), today announced a voluntary recall of approximately 32,000 "Master" number 2551 battery-operated smoke alarms and number 2553 dual-powered smoke alarms made late in 1975 and during part of 1976. The recalled smoke alarms can be identified by the following range of serial numbers: 1 to 10,000; 17,735 to 20,000 and 2,000,001 to 2,020,000. The serial number is located on the back cover of the smoke alarm under the mounting bracket. Some of the units may fail to alarm when the relative humidity is over 70% in the home because they were inadequately cleansed of soldering flux after initial assembly. Other units may not be sensitive enough to alarm at minimum smoke levels set by industry standards. The company has received one complaint from a consumer who noticed an alarm did not function properly during a routine test. Consumers who own a "Master" smoke alarm with a serial number that falls within the range of 1 to 10,000; 17,735 to 20,000 or 2,000,00l to 2,020,000 are asked to write: Master Lock Company, 2600 N. 32nd Street, Milwaukee, Wisconsin 53210, Attention: Department #16, including their name, address, telephone and serial number of the alarm. The company will promptly send the consumer a form detailing full return instructions. The units will either be replaced or corrected, depending on the problem, without cost to the consumer. Consumers who require additional information should write to the company

Hazard

Fire & Fire-Related Burn

Machine access

This record, with every extracted field, the source record (contact text and images withheld) and provenance: GET https://api.data.aroqon.com/v1/product-recalls/cpsc-77081. Look up a model number or UPC with /v1/product-recalls/lookup?code=…. About the dataset · free and paid keys.

Source: U.S. Consumer Product Safety Commission recall notice (US Government work). Not affiliated with or endorsed by CPSC. Structured by Data Foundry (product-recall-structuring@2); last changed 2026-09-28. Always confirm with the agency notice.